SR560 (Discontinued)

Dual Channel Alarm Unit for mA/V Signals

SR560 is designed for monitoring mA or V signals in the process industry.
The two channels are fully independent.
The SR560 is specially designed for reliable safety triggering without false alarms.

High configuration flexibility allows for adaptation to required alarm functions.

  • Two fully independent isolated channels
  • Current and voltage input
  • Reliable and interference free safety alarm without false alarms
  • High configuration flexibility with solder jumpers
  • Adjustable time delay, hysteresis and relay functions
  • Available for AC or DC power supply
  • DIN-rail mounting
  • Plug-in screw terminals
Category: .

Technical Specification

No. of channelsTwo, independent selection of input signal
Input Voltage0(0,2)-1 V, 0(1)-5 V, 0(2)-10 V
Input impedance10 MΩ
Input Current0(4)-20 mA (standard)
Input impedance51 Ω
Maximum input level200 % of input span
Output Relay 1 & 2One per channel 1-pole switch over contact
Selectable High or Low alarmJumpers on PCB (standard: High)
Adjustable alarm set-pointFront 15-turn potentiometers / test connectors
Selectable alarm delay0.4 s (standard) or 2 s, changeable on PCB
Adjustable hysteresis0.35 % (standard) to 80 % with front 15-turn
Selectable normally active or passive functionJumpers on PCB (standard: normally active)
Operation temperature-20 to +60 °C / -4 to +140 °F
Galvanic isolation
AC versions
Input to relay outputs3 700 VAC, 1 min
Input to power supply3 700 VAC, 1 min
Relay outputs to power supply3 700 VAC, 1 min
Between channels1 500 VAC, 1 min
DC version
Input to relay outputs1 500 VAC, 1 min
Input to power supply1 500 VAC, 1 min
Relay outputs to power supply1 500 VAC, 1 min
Between channels1 500 VAC, 1 min
Power supply
 AC versions 230 VAC, -15..+10 %, 45..75 Hz
115 VAC, -15..+10 %, 45..75 Hz
DC version19 to 60 VDC
Typical accuracyTrip point ± 0.1 % of span
ConnectionsPlug-in terminals Stranded, ≤ 2.5 mm2, AWG 14
MountingRail acc. to DIN EN 50022, 35 mm

Documents

Request a quote

  • For example approvals and configuration
  • This field is for validation purposes and should be left unchanged.