SR360 (Discontinued)
Alarm Unit with Current and Voltage Input and Double Relay Outputs
SR360 is designed for monitoring current and voltage signals in the process industry.
Two output relays with individually adjustable trip functions are available.
LED’s in the front indicate alarm state and correct power supply.
- Current and voltage input
- Two relay outputs with independent switch functions
- Monostable relays for safe tripping at power failure
- SPDT relays with 6 A switch capacity
- High configuration flexibility with DIP switches
- Trip levels and hysteresis adjustable from the front
- Three front LED’s for trip indication and power supply monitoring
- 4 kV isolation between input, output and power supply
- Protective Separation acc. to EN 50178
- Universal 24 V AC and DC power supply
- DIN-rail mounting
Technical Specification
Input Current | 0(4) to 20 mA or ±20 mA (switch selectable) |
Input impedance | 5 Ω |
Maximum overload | 200 mA |
Input Voltage | 0 to 10 V or ±10 V (switch selectable) |
Input impedance | 1 MΩ |
Maximum overload | 250 V |
Output, Relay 1 & 2 | |
Relay contacts | 1-pole switch over contact (SPDT) |
Contact rating | 250 VAC/DC, 6 A, 1 500 VA |
Relay function | Monostable, Normally active or passive (switch selectable) |
Alarm functions, relay 1 | High/Low alarm (switch selectable) |
Alarm functions, relay 2 | High/Low alarm or Power failure alarm (switch selectable) |
Alarm indication | Alarm state indicated by yellow LED |
Response time | Ca. 20 ms (fixed) |
Operation temperature | -20 to +60 °C / -4 to +140 °F |
Galvanic isolation | |
Input / power supply / relay outputs | 4 kVAC, 1 min |
Relay 1 / Relay 2 | 2,5 kVAC, 1 min |
Power supply | |
Voltage | 24 VAC/DC ±15 %, 48 to 62 Hz (AC supply) |
Power consumption | AC: ca. 2 VA, DC: ca. 1 W |
Typical accuracy | Trip point: ±0.2 % of span |
Mounting | Rail acc. to DIN EN 50022, 35 mm |