SR360 (Discontinued)

Alarm Unit with Current and Voltage Input and Double Relay Outputs

SR360 is designed for monitoring current and voltage signals in the process industry.
Two output relays with individually adjustable trip functions are available.
LED’s in the front indicate alarm state and correct power supply.

  • Current and voltage input
  • Two relay outputs with independent switch functions
  • Monostable relays for safe tripping at power failure
  • SPDT relays with 6 A switch capacity
  • High configuration flexibility with DIP switches
  • Trip levels and hysteresis adjustable from the front
  • Three front LED’s for trip indication and power supply monitoring
  • 4 kV isolation between input, output and power supply
  • Protective Separation acc. to EN 50178
  • Universal 24 V AC and DC power supply
  • DIN-rail mounting
Category: .

Technical Specification

Input Current0(4) to 20 mA or ±20 mA (switch selectable)
Input impedance5 Ω
Maximum overload200 mA
Input Voltage0 to 10 V or ±10 V (switch selectable)
Input impedance1 MΩ
Maximum overload250 V
Output, Relay 1 & 2
Relay contacts1-pole switch over contact (SPDT)
Contact rating250 VAC/DC, 6 A, 1 500 VA
Relay functionMonostable, Normally active or passive (switch selectable)
Alarm functions, relay 1High/Low alarm (switch selectable)
Alarm functions, relay 2High/Low alarm or Power failure alarm (switch selectable)
Alarm indicationAlarm state indicated by yellow LED
Response timeCa. 20 ms (fixed)
Operation temperature-20 to +60 °C / -4 to +140 °F
Galvanic isolation
Input / power supply / relay outputs4 kVAC, 1 min
Relay 1 / Relay 22,5 kVAC, 1 min
Power supply
Voltage24 VAC/DC ±15 %, 48 to 62 Hz (AC supply)
Power consumptionAC: ca. 2 VA, DC: ca. 1 W
Typical accuracyTrip point: ±0.2 % of span
MountingRail acc. to DIN EN 50022, 35 mm

Documents

Request a quote

  • For example approvals and configuration
  • This field is for validation purposes and should be left unchanged.