IsoPAQ-610

Transmitter repeater for powering and
isolation of 2-,3- and 4-wire transmitters

The Repeater Power Supply IsoPAQ-610 is used to supply and separate 2- and 3-wire SMART Transmitters and active sensor signals with HART communication.

It supplies the transmitter with power and transmits the measuring signal with high accuracy galvanic isolated to the output. Alternative the measuring input accepts active 0/4 … 20 mA signals from 4-wire transmitters.

In addition to the analog signal, the IsoPAQ-610 also transmits data protocols for HART communication. It allows bidirectional communication with the field device from every point of the cabling.

The auxiliary power can be supplied via the connection terminals or via the optional In-Rail-Bus connector. A green LED on the front of the unit has been provided to monitor the power supply.

  • Universal operation of SMART Transmitters
    Energization and separation of field located 2-, 3- and 4-wire transmitters
  • 3-Port isolation
    Protection against erroneous measurements due to parasitic
    voltages or ground loops
  • Extremely slim design
    6.2 mm slim housing for a simple and space saving installation
  • Optional In-Rail-Bus mounting rail connector
    Allows for fast and economical installation
  • Skyddsseparation enligt EN 61140
    Konstruktionen och den höga isolationsnivån skyddar servicepersonal och enheter nedströms mot otillåten hög spänning
  • Protective Separation acc. to EN61140
    Protects service personnel and downstream devices against
    impermissibly high voltage

Technical Specification

Input
Input signal0/4…20 mA  (4… 20 mA with HART signal)
Input resistance50 Ω
Over load50 mA / 30 V
Transmitter supply (Tx)16 V (open circuit voltage/short circuit current < 22 V/35 mA)
Communication signalBidirectional HART transmission, internal AC impedance 250 Ω
Output
Output signal0/4…20 mA  (4… 20 mA with HART signal)
Load ≤ 12 V (600 Ω at 20 mA)
Linear transmission range–1 … +110 %
Residual ripple< 10 mVrms
General data
Transmission error< 0.1 % full scale
Temperature coefficient1)< 100 ppm/K
Cut-off frequency -3 dB100 Hz,   >2,5 kHz HART-signal
Response time T997 ms
Test voltage3 kV AC, 50 Hz, 1 min.
Input against output against power supply
Working voltage (Basic insulation)600 V AC/DC for overvoltage category II and contamination class 2 acc. to EN 61010-1
Protection against dangerous body currentsProtective Separation by reinforced insulation acc. to EN 61010-1 up to 300 V AC/DC for overvoltage category II and contamination class 2 between input and output and power supply.
Ambient temperatureOperation
– 25 °C to + 70 °C (– 13 to + 158 °F)
Transport and storage
– 40 °C to + 85 °C (– 40 to + 185 °F)
Power supply24 VDC  16.8 … 31.2 V DC, approx. 1,3 W
EMCEN 61326-1
Construction62 x 96,5 x 107 mm , skyddsklass IP 20, monteras på 35 mm skena enl. EN 60715
WeightApprox. 70 g

Documents

Request a quote

  • For example approvals and configuration
  • This field is for validation purposes and should be left unchanged.