IsoPAQ-641
High-performance isolation transmitter for mA/V Signals with calibrated range selection
The Isolation Amplifier IsoPAQ-641 is used for isolation and conversion of 0/4 … 20 mA and 0/2 … 10 V standard signals.
The input and output range of IsoPAQ-641 can be easily set by using DIP switch. Due to the calibrated range selection no further adjustment is necessary. Also the cut-off frequency can be adapted to the measurement task by using the DIP Switch.
The auxiliary power can be supplied via the connection terminals or via the optional In-Rail-Bus connector. A green LED on the front of the unit has been provided to monitor the power supply.
- Calibrated signal setting via DIP switch
Input and output range can be set by using DIP switch – high
precision without any further adjustment
- 3-Port Isolation
Protection against erroneous measurements due to parasitic
voltages or ground loops - Extremely slim design
6.2 mm slim housing for a simple and space saving
DIN rail mounting - Optional In-Rail-Bus mounting rail connector
Allows for fast and economical installation - Protective Separation acc. to EN 61140
Konstruktionen och den höga isolationsnivån skyddar servicepersonal och enheter nedströms mot otillåten hög spänning
- Maximum reliability
No maintenance costs
Technical Specification
Input | |
Input signal (calibrated switchable) | 0 … 20 mA, 4 … 20 mA 0 … 10 V, 2 … 10 V |
Input resistance | Current input ≤ 25 Ω Voltage input ≥ 100 kΩ |
Overload | Current input < 50 mA Voltage input < 30 V |
Output | |
Output signal (calibrated switchable) | 0 … 20 mA, 4 … 20 mA 0 … 10 V, 2 … 10 V |
Load | Current output: ≤ 12 V (600 Ω at 20 mA) Voltage output: ≤ 5 mA (2 kΩ at 10 V) |
Linear transmission range | –1 … +110 % |
Residual ripple | < 10 mVrms |
General Data | |
Transmission error | < 0.1 % full scale |
Temperature coefficient | < 100 ppm/K |
Cut-off frequency -3 dB | 5 kHz, 100 Hz, 10Hz |
Response time T99 | 150 µs, 7 ms, 70 ms |
Test voltage | 3 kV AC, 50 Hz, 1 min. Input against output against power supply |
Working voltage (Basic insulation) | 600 V AC/DC for overvoltage category II and pollution degree 2 acc. to EN 61010-1 |
Protection against electrical shock | Protective separation according to EN 61140 by reinforced insulation in accordance with EN 61010-1 up to 300 V AC/DC for overvoltage category II and pollution degree 2 between all circuits. |
Ambient temperature | Operation – 25 °C to + 70 °C (– 13 to + 158 °F) Transport and storage – 40 °C to + 85 °C (– 40 to + 185 °F) |
Power supply | 24 V DC voltage range 16.8 V … 31.2 V, approx. 0.7 W |
EMC | EN 61326-1 |
Construction | 62 x 96,5 x 107 mm , protection class IP 20, mounting on 35 mm DIN rail acc. to EN 60715 |
Weight | Approx. 70 g |