IsoPAQ-641

High-performance isolation transmitter for mA/V Signals with calibrated range selection

The Isolation Amplifier IsoPAQ-641 is used for isolation and conversion of 0/4 … 20 mA and 0/2 … 10 V standard signals.

The input and output range of IsoPAQ-641 can be easily set by using DIP switch. Due to the calibrated range selection no further adjustment is necessary. Also the cut-off frequency can be adapted to the measurement task by using the DIP Switch.

The auxiliary power can be supplied via the connection terminals or via the optional In-Rail-Bus connector. A green LED on the front of the unit has been provided to monitor the power supply.

  • Calibrated signal setting via DIP switch
    Input and output range can be set by using DIP switch – high
    precision without any further adjustment
  • 3-Port Isolation
    Protection against erroneous measurements due to parasitic
    voltages or ground loops
  • Extremely slim design
    6.2 mm slim housing for a simple and space saving
    DIN rail mounting
  • Optional In-Rail-Bus mounting rail connector
    Allows for fast and economical installation
  • Protective Separation acc. to EN 61140
    Konstruktionen och den höga isolationsnivån skyddar servicepersonal och enheter nedströms mot otillåten hög spänning
  • Maximum reliability
    No maintenance costs

Technical Specification

Input
Input signal
(calibrated switchable)
0 … 20 mA,  4 … 20 mA
0 … 10 V,  2 … 10 V
Input resistanceCurrent input ≤ 25 Ω
Voltage input ≥ 100 kΩ
OverloadCurrent input < 50 mA
Voltage input < 30 V
Output
Output signal
(calibrated switchable)
0 … 20 mA,  4 … 20 mA
0 … 10 V,  2 … 10 V
LoadCurrent output: ≤ 12 V (600 Ω at 20 mA)
Voltage output: ≤ 5 mA (2 kΩ at 10 V)
Linear transmission range–1 … +110 %
Residual ripple< 10 mVrms
General Data
Transmission error< 0.1 % full scale
Temperature coefficient< 100 ppm/K
Cut-off frequency -3 dB5 kHz,   100 Hz,  10Hz
Response time T99150 µs,   7 ms,     70 ms
Test voltage3 kV AC, 50 Hz, 1 min.
Input against output against power supply
Working voltage (Basic insulation)600 V AC/DC for overvoltage category II and pollution degree 2 acc. to EN 61010-1
Protection against electrical shockProtective separation according to EN 61140 by reinforced insulation in accordance with EN 61010-1 up to 300 V AC/DC for overvoltage category II and pollution degree 2 between
all circuits.
Ambient temperatureOperation
– 25 °C to + 70 °C (– 13 to + 158 °F)
Transport and storage
– 40 °C to + 85 °C (– 40 to + 185 °F)
Power supply24 V DC voltage range 16.8 V … 31.2 V, approx. 0.7 W
EMCEN 61326-1
Construction62 x 96,5 x 107 mm , protection class IP 20, mounting on 35 mm DIN rail acc. to EN 60715
WeightApprox. 70 g