IsoPAQ-612
2-channel Loop Powered Isolator for separation of 0(4)-20 mA Signals
The input loop-powered isolator IsoPAQ-612 provides galvanic separation for 0(4) … 20 mA standard signals, while transferring the measurement signal to the output with a high degree of accuracy.
The unit avoids interference voltage carry-over and effectively suppressing parasitic noise. The very low drop voltage of 2.3 V and the high level of accuracy work together to make the IsoPAQ-612 the first choice in system design.
Intelligent design and their consequential avoidance of highly integrated components result in extremely long service lives and reliability – without any falsification of the measurement signal.
The IsoPAQ-612 requires no additional power supply since the auxiliary power is obtained from the input signal without distorting it. This not only saves costs during installation, but also increases reliability..
- Galvanic isolation across input and output
Protection against erroneous measurements due to parasitic
voltages or ground loops - No power supply required
Saving costs since wiring is reduced and line influences are omitted - Extremely slim design
Only 3.1 mm DIN-rail per channel - Protective Separation acc. to EN 61140
Protects service personnel and downstream devices against
impermissibly high voltage - Maximum reliability
No maintenance costs
Technical Specification
Input | ||||
Input signal | 0(4)-20 mA | |||
Start-up current | < 200 mA | |||
Voltage drop | Ca. 2.3 V at 20 mA | |||
Overload | ≤ 50 mA, 30 V | |||
Output | ||||
Output signal | 0(4)-20 mA | |||
Load | 600 Ω | |||
Response time T99 | 5 ms | |||
Residual ripple | < 10 mVrms | |||
General Data | ||||
Transmission error | < 0.1 % full scale | |||
Load error | < 0.05 % of measured value / 100 Ω load | |||
Temperature coefficient | < 100 ppm/K | |||
Test voltage | 3 kV AC, 50 Hz, 1 min. all circuits against one another | |||
Working voltage (Basic insulation) | 600 V AC/DC for overvoltage category II and pollution degree 2 acc. to EN 61010-1 | |||
Protection against electrical shock | Protective separation according to EN 61140 by reinforced insulation in accordance with EN 61010-1 up to 300 V AC/DC for overvoltage category II and pollution degree 2 between all circuits. | |||
Ambient temperature | Operation – 25 to + 70 °C (– 13 to + 158 °F) Transport and Storage – 40 to + 85 °C (– 40 to + 185 °F) | |||
EMC | EN 61326-1 | |||
Construction | 62 x 96,5 x 107 mm , protection class IP 20, mounting on 35 mm DIN rail acc. to EN 60715 | |||
Weight | Approx. 70 g |