DA561 (Discontinued)

Isolation Transmitter for mA/V Signals with 2-wire Transmitter Supply

DA561 is specially designed for signal isolation and load amplification in the process industry.
A 2-wire transmitter can be connected to and supplied from the isolation amplifier. DA561 maintains a high isolation level (1,5 kV) between input and output. Current and voltage can be chosen independently as input and output signals.

  • Current and voltage input
  • Current and voltage output
  • Direct connection of 2-wire transmitter
  • Output test terminals
  • 1 500 V isolation level
  • Short response time
  • High noise immunity
  • Available for AC or DC power supply
  • DIN-rail mounting
  • Plug-in screw terminals
Category: .

Technical Specification

Input Voltage 0(0,2)-1 V, 0(1)-5 V, 0(2)-10 V
Input impedance1 MΩ
Input Current0(4)-20 mA (standard setting)
Input impedance11,9 Ω
Maximum input level200 % of measurement span
Output Voltage0(0,2)-1 V, 0(1)-5 V, 0(2)-10 V, short circuit protected
Minimum load500 kΩ (error effect
Voltage limitationApprox. 56 V
Output Current0(4)-20 mA, open or short circuit protected
(standard setting)
Maximum load600 Ω
Current limitationApprox. 23 mA
Test outputmA instrument, Ri ≤ 10 Ω
Transmitter supply voltage19 VDC, max. ripple 100 mV p-p
Operation temperature-20 to +60 °C / -4 to +140 °F
Galvanic isolationAC & DC version
Input to output 1 500 VAC, 1 min
Input/output to power supply 2 200 VAC, 1 min
Power supply AC versions230 VAC, -15..+10 %, 45..75 Hz,
115 VAC, -15..+10 %, 45..75 Hz
Power supply DC version19 to 60 VDC
Typical accuracy±0,15 % of span
ConnectionsPlug-in terminals Stranded, ≤ 2.5 mm2, AWG 14
MountingRail acc. to DIN EN 50022, 35 mm

Documents

Request a quote

  • For example approvals and configuration
  • This field is for validation purposes and should be left unchanged.