SR361

Alarm Unit with Current and Voltage Input and Double Relay Outputs

SR361 is designed for monitoring current and voltage signals in the process industry.
Two output relays with individually adjustable trip functions are available.
LED’s in the front indicate alarm state and correct power supply.

  • Current and voltage input
  • Direct connection to 2-wire transmitters with built-in supply
  • Two relay outputs with independently or simultaneosly switch functions
  • Monostable relays for safe tripping at power failure
  • SPDT relays with 6 A switch capacity
  • High configuration flexibility with DIP switches
  • Trip levels and hysteresis adjustable from the front
  • Three front LED’s for trip indication and power supply monitoring
  • 4 kV isolation between input, output and power supply
  • Protective Separation acc. to EN 61010
  • 24 V DC power supply
  • DIN-rail mounting
Category: . Tag: .

Technical Specification

Input Current0(4) to 20 mA
Input impedance5 Ω
Maximum overload200 mA
Input Voltage0(2) to 10 V
Input impedance120 kΩ
Maximum overload300 V
2-wire Transmitter Supply +Us16 V at UPower = 24 V, (13 … 22 V depending on the supply voltage) current limited ≤ 30 mA
Output, Relay 1 & 2
Relay contacts1-pole switch over contact (SPDT)
Contact rating max.AC: 250 V / 6 A, 1500 VA
DC: 250 V / 0.2 A, 115 V / 0.3 A, 30 V / 6 A
Relay functionMonostable, Normally active or passive (switch selectable)
Alarm functions, relay 1 & 2High/Low alarm (switch selectable)
Alarm indicationAlarm state indicated by yellow LED
Response timeapprox. ca. 20 ms
Operation temperature-20 to +60 °C / -4 to +140 °F
Galvanic isolation
Input / power supply / relay outputs4 kVAC, 1 min
Relay 1 / Relay 23 kVAC, 1 min
Power supply
Voltage24 VAC/DC ±15 %, 48 to 62 Hz (AC supply). 24 V CD, ± 15 %, 1.0 W
Typical accuracyTrip point: ±0.2 % of span
Mounting35 mm DIN rail acc. to EN 60715

Documents

Request a quote

  • For example approvals and configuration
  • This field is for validation purposes and should be left unchanged.